Low Frequency Online UPS GP9315C 10-120KVA

Short Description:

3Ph in/1Ph out Online UPS with high power factor 0.9, use AC-DC-AC converter,support 6 units ups parallel operation,EPO/RS232/Bypass available. 6pulse or 12 pulse optional.


Product Detail

Product Description

Key Features:
    1.Use advanced 6th generation DSP and full digital control technologies to realize higher system stability.
    2.Output power factor is 0.9, carrying capacity than conventional UPS with 10% above, as users reduce investment cost.
    3.Advanced distributed active parallel technology can realize parallel operation of 6PCS UPS units without the need of centralized bypass cabinet.
    4.6-inch extra large LCD that can display 12 language (Chinese ,English,Russian,Spanish,French and so on).
    5.Extra wide input voltage and frequency range make it adapt to severe power grid environment.
    6.Intelligent battery management maintains battery automatically to prolong the battery life.
    7.Standard input/output filter improves the system EMC performance.
    8.Extra strong capability to withstand output overload and short circuit, ensuring the system stability and system safety under extreme conditions.
    9.Layered independently-sealed ventilation channel and re-dundant fan, circuit boards with protective paints and a dust filter embedded make it highly efficient to dissipate heat and protect the product effectively under severe environment.

Specification

Model GP9315C    10-120KVA
Rectifier    Type 6p 12p 6p 12p 6p 12p 6p 12p 6p 12p 12P 12P 12P
Rated    Nominal 10KVA/
9KW
20KVA/
18KW
30KVA/
27KW
40KVA/
36KW
60KVA/
54KW
80KVA/
72KW
100KVA/
90KW
120KVA/
108KW
Rated    input voltage 380/400/415VAC    3-phase 4-wire
Rated    frequency 50/60HZ
Input parameters 
Input    voltage range ±25%
Input    frequency range 45Hz~65Hz
Input    soft start function 0-100%      5-300settable
Input    power factor >0.8
Input harmonic    current (THDi) <20%
Bypass 
Bypass    voltage range -20%~+15%
Bypass    frequency range 50/60HZ±10%
Output parameters 
Inverter    output voltage 220/230/240VAC    1-phase 3-wire
Voltage    stability ±1%(Steady    status),±3%(Transient status)
Frequency 50/60Hz
Mains power    synchronization window ±5%
Actually    measured frequency accuracy (internal clock) 50/60Hz±0.05Hz
Output    power factor 0.9(Output    90kW per 100kVA)
Transient    response time <5ms
Inverter overload    capability At    0.9 power factor, 110% for 1 hour, 125% for 10 minutes and 150% for 60s
Short circuit    current from inverter 3ph    1.5ln for 5seconds,1ph 2.9ln for 5seconds
DC Voltage 360/384/432/480VDC
Maximum Bypass    capability 1000%    for 100ms
Phase Shift characteristic With 100% balanced load <1°
With 100% imbalanced load   <1°
Total harmonic Distortion(THDv) 100%    linear load <1%
100% non-linear load <3%
System    efficiency (full load) Up    to 94% (inverter efficiency is up to 98%)
Rectifier output parameters
Charger    output voltage stability 1%
DC    ripple voltage ≤1%
Operating environment 
Operating    temperature range 0~40°C
Storage    temperature -25~70°C(Without    battery)
Relative    humidity 0~95%    No condensation
Maximum    Operating Height ≤Elevation 1000m, for elevation    above 1000m, derate by 1% for every increase of 100m 
Noise    (1m) 58-68dB
Protection    level IP20
Standard Safety:    IEC60950-1 IEC62040-1-1 UL1778 EMC IEC62040-2 CLASS C2 EN50091-2 CLASS A    Design and Test IEC62040-3
Physical Parameters
Weight(kg) 980 1420 1200 1750 1350 2000 1600 2200 2100 2750 3690 6390 7390
Dimension(WxDxh)mm 900*855*1900 1250*855*1900 1640*855*1900 1250*855*1900 1640*855*1900 2280*855*1900 2835*1000*1950 3955*1090*1950

Packing & Delivery