Quick Details
Place of Origin: | Guangdong, China | Application: | Networking |
Brand Name: | SOROTEC | Name: | 10kva Online UPS |
Model Number: | HP9335C Plus | Output voltage: | 208/220/230/240VAC(Ph-N) |
Phase: | Three Phase | AC Voltage Regulation: | ± 1% |
Protection: | Short Circuit | Frequency Range (Synchronized Range): | 46Hz ~ 54 Hz @ 50Hz system ; 56Hz ~ 64 Hz @ 60Hz system |
Output Voltage: | 220VAC/230VAC/240VAC | Frequency Range (Batt. Mode): | 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz |
Type: | On-line | Current Crest Ratio: | 3:1 max |
Operation Temperature: | 0 ~ 40°C (the battery life will down when > 25°C) | Operation Altitude: | <1000m |
Operation Humidity: | <95 % and non-condensing | Harmonic Distortion: | ≤ 2 % @ 100% Linear Load; ≤5 % @ 100% Non-linear Load |
Supply Ability
Packaging & Delivery
EPO Active power factor correction Online UPS HP9335C Plus
Key Features:
1.Its cut-edge digital technology of DSP (Digital Signal Processor), can greatly improve the products performance and system reliability, and deliver a compact integratin with higher power density ;
2.Output power factor up to 0.8 – applicable to the tendency of future load evolution, and deliver higher payload capacity;
3.Total power factor up to 90% can minimize the power loss of UPS and save utilization cost for user;
4.Emergency Power Off (EPO): UPS can be instantly shut off in case of any emergency;
5.Compliance with EMC requirements of IEC61000-4, provide your device a clean electric environment.
6.Active power factor correction (PFC) technology allows the input power fact or approaching to 1, dramatically reducing the immunity on utility grid;
7.Excellent input frequency range makes UPS suitable to different power supply devices, i.e. generator set;
8.Parallel Kit: realize the parallel extension and redundancy function, offer more flexibility and safety for user’s power supply planning;
9.Compact Design, Lower Noise;
Product Descriptions of Ups 15Kva
MODEL | HP9335C Plus 10-30KVA | ||||||||
10K | 10K-XL | 15K | 15K-XL | 20K | 20K-XL | 30K | 30K-XL | ||
CAPACITY | 10KVA / 9KW | 15KVA / 13.5KW | 20KVA / 18KW | 30KVA / 27KW | |||||
PHASE | 3 Phase with Neutral | ||||||||
INPUT | |||||||||
Voltage Range | Low Line Loss | 110 VAC(Ph-N) ± 3 % at 50% Load ; 176 VAC(Ph-N) ± 3 % at 100% Load | |||||||
Low Line Comeback | Low Line Loss Voltage + 10V | ||||||||
High Line Loss | 300 VAC(Ph-N) ± 3 % | ||||||||
High Line Comeback | High Line Loss Voltage – 10V | ||||||||
Phase | Three phase with ground | ||||||||
Power Factor | ≥ 0.99 at 100% Load | ||||||||
OUTPUT | |||||||||
Output voltage | 208/220/230/240VAC(Ph-N) | ||||||||
AC Voltage Regulation | ± 1% | ||||||||
Frequency Range (Synchronized Range) | 46Hz ~ 54 Hz @ 50Hz system ; 56Hz ~ 64 Hz @ 60Hz system | ||||||||
Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz | ||||||||
Overload | AC mode | 100%~110%: 10min ; 110%~130%: 1min ; >130% : 1sec | |||||||
Battery mode | 100%~110%: 30sec ; 110%~130%: 10sec ; >130% : 1sec | ||||||||
Current Crest Ratio | 3:1 max | ||||||||
Harmonic Distortion | ≤ 2 % @ 100% Linear Load; ≤ 5 % @ 100% Non-linear Load | ||||||||
Transfer Time | Line←→Battery | 0 ms | |||||||
Inverte←→Bypass | 0 ms (When phase lock fails, <4ms interruption occurs from inverter to bypass) | ||||||||
Line←→ECO | <10 ms | ||||||||
EFFICIENCY | |||||||||
AC mode | > 89% | > 89% | > 89% | > 90% | |||||
Battery Mode | > 86% | > 88% | > 87% | > 89% | |||||
BATTERY | |||||||||
Standard Model | Type | 12 V / 9 Ah | 12 V / 9 Ah | 12 V / 9 Ah | 12 V / 9 Ah | ||||
Numbers | 20(18-20 adjustable) | 2 x 20(18-20 adjustable) | 2 x 20(18-20 adjustable) | 3 x 20(18-20 adjustable) | |||||
Recharge Time | 9 hours recover to 90% capacity | ||||||||
Charging Current | 1.0 A ± 10% (max.) | 2.0 A ± 10% (max.) | 2.0 A ± 10% (max.) | 4.0 A ± 10% (max.) | |||||
Charging Voltage | 273 VDC ± 1% | ||||||||
Long-run Model | Type | Depending on applications | |||||||
Numbers | 18-20 | ||||||||
Charging Current | 4.0 A ± 10% (max.) | 4.0 A ± 10% (max.) | 4.0 A ± 10% (max.) | 12.0 A ± 10% (max.) | |||||
Charging Voltage | 273 VDC ± 1% | ||||||||
PHYSICAL | |||||||||
Standard Model | Dimension,DxWxH(mm) | 832 X250X894 | 832 X250X1275 | ||||||
Long-run Model | Dimension,DxWxH(mm) | 609 X250X768 | 832 X250X828 | ||||||
ENVIRONMENT | |||||||||
Operation Temperature | 0 ~ 40°C (the battery life will down when > 25°C) | ||||||||
Operation Humidity | <95 % and non-condensing | ||||||||
Operation Altitude | <1000m | ||||||||
Acoustic Noise Level | Less than 58dB @ 1 Meter | Less than 60dB @ 1 Meter | |||||||
MANAGEMENT | |||||||||
Smart RS-232 / USB | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and MAC | ||||||||
USB | Power management from SNMP manager and web browser |